Provisional engineering estimates — not validated for design use.The following figures are theoretical reference-case calculations, not measured, certified or guaranteed Lo-Float performance. Independent technical review and physical validation are outstanding. Do not use these figures to select operating temperatures or size a heating system.
Indicative upward heat output and average finished floor temperatures for Lo-Float at 150mm pipe centres, assuming a concrete sub-floor and a room temperature of 20°C.
Indicative upward heat output (W/m²)
* Modelled local surface temperature reaches or exceeds the assumed threshold. ** Modelled average surface temperature reaches or exceeds the threshold. Unmarked values are not confirmation of safe operation. Values are unrestricted theoretical results, not permissible design outputs.
Average finished floor surface temperature (°C)
* Modelled local surface temperature reaches or exceeds the assumed threshold. ** Modelled average surface temperature reaches or exceeds the threshold. Unmarked values are not confirmation of safe operation. Values are unrestricted theoretical results, not permissible design outputs.
Illustrative temperature thresholds
†Extrapolated beyond the modelled 30–55°C range; not a recommended operating condition. Thresholds are calculated from the reference model and are not approved maximum water temperatures. The lower of applicable standard and flooring, adhesive and underlay manufacturer limits must be observed, including interface temperatures.
Assumed floor covering thermal resistance
Tiles: 0.010 m²K/W | LVT: 0.025 m²K/W | Engineered wood: 0.100 m²K/W | Carpet and underlay (1.5 tog): 0.150 m²K/W | Carpet and underlay (2.5 tog): 0.250 m²K/W.
Technical information & performance limitations
The calculations use a two-dimensional steady-state numerical reference model of 16 × 2mm PE-RT pipe at 150mm centres in 25mm routed XPS insulation (thermal conductivity 0.030 W/mK), with 16mm wide and 16mm deep rounded channels and a 10mm self-levelling compound layer above the pipe (thermal conductivity 1.50 W/mK). A 100mm concrete sub-floor (1.70 W/mK), 20°C room and lower boundary temperatures, pipe conductivity of 0.40 W/mK, ideal material contact and a constant surface heat transfer coefficient of 10 W/m²K are assumed. Floor finishes are represented by equivalent homogeneous layers. The model assumes compound fills the available space above the pipe within the channel.
Outputs refer to upward heat emission per square metre of active heated floor, not total room area or total heat supplied by the water. Mean water temperature is not flow temperature. Actual performance depends on construction, insulation, contact quality, floor finish and adhesive properties, water temperatures, flow rates, circuit layout and installation conditions. Sensitivity calculations indicate that poorer contact and other adverse conditions can substantially reduce output. No minimum output is guaranteed by this table.
The self-levelling compound and compatible primer must be specifically approved by their manufacturer for the proposed application over routed XPS insulation panels, for water underfloor heating and for the specified thickness. Thermal conductivity alone does not establish suitability. Approval of the reference construction remains outstanding.
Average floor temperatures do not establish maximum local or interface temperatures. The assumed thresholds of 29°C for tiles and 27°C for other finishes are illustrative, not universal material limits. Observe applicable standards and all flooring, adhesive and underlay manufacturer requirements. Suitable temperature controls and project-specific assessment are required.
These provisional estimates have not been independently validated or tested or certified to BS EN 1264. They are not a declaration of conformity, guaranteed performance, installation approval or project-specific design. Do not rely on them for system selection, sizing, specification or commissioning. Obtain project-specific heat loss and system design calculations and verified performance information from HydroHeat before proceeding.
Nothing in this guidance excludes or restricts liability where doing so would be prohibited by law, or affects applicable statutory rights.